SCB - 99 h
|
Safety function
|
Emergency stop monitoring, safety guard monitoring, light grids monitoring, furnaces in continuous operation, stop category 0/1
|
Certified according to
|
EN ISO 13849-1:2015, EN 50156-1:2015, EN62061:2005 + AC: 2010 + A1:2013 + A2:2015, IEC 61508 Parts 1-7:2010, IEC 61511-1:2016, EN 746-2:2010
|
Approvals
|
CE, TUV
|
Supply voltage
|
UB: DC 24 V (+ 10 /- 15 %)
|
Number of safe outputs
|
Up to 4 (depending on variant)
|
Switching capability per safe relay outputs
|
AC -15: 3 A / 250 V; DC -13: 2 A / 24 V
|
Switching capability for safe semiconductor outputs
|
UB / 500 mA; PNP; short circuit proof
|
Number of auxiliary semiconductor outputs
|
2
|
Switching capability for auxiliary outputs
|
C1: UB / 500 mA; PNP; short circuit proof C2: UB / 50 mA; PNP; short circuit proof
|
Number of non time-delayed outputs
|
Up to 4 (depending on variant)
|
Number of time-delayed outputs
|
Up to 4 (depending on variant)
|
Adjustable delay
|
0 - 99 h
|
Number of safe inputs
|
1 x 2 channel
|
Starting behavior
|
Automatic start or manual, monitored start
|
PL; Cat.; SILCL (EN ISO 13849-1; EN/IEC 62061)
|
PL e; Cat. 4; SILCL 3
|
Dimensions
|
22.5 x 99 x 118 mm
|
SCB incl. plug-in screw terminals
|
|
Order No. SCB, 2 seminconductor and 2 relay contacts
|
474462
|
Order No. SCB, 3 seminconductor contacts
|
474482
|
Order No. SCB, 2 relay contacts
|
474492
|
SCB incl. plug-in spring terminals
|
|
Order No. SCB, 2 seminconductor and 2 relay contacts
|
475462
|
Order No. SCB, 3 seminconductor contacts
|
475482
|
Order No. SCB, 2 relay contacts
|
475492
|