Click to reach us online

MINOS SLxD - EN 50156-1

Safe Firing MINOS SLxD - EN 50156-1

Features

  • Use up to PL, Cat. 4, SILCL3 (bound variant)
  • Stop category 0 according to EN 60204-1
  • 1 two-channel safe access
  • 1 safe solid state output (PNP)
  • 1 auxiliary output (PNP)
  • Automatic or monitored manual start
  • 6.2 mm width
  • Comprehensive monitoring with front LEDs

MINOS SLxD

Safety function

Safety emergency stop, safety doors, light curtains, contact reinforcement, OSSD, continous operation of furnaces , stopp category 0

Certified according to

EN ISO 13849-1; IEC 62061; IEC 61508;
EN 50156-1; EN 746-2IEC 61511-1; EN 60204-1

Approvals

CE, TUV

Operating voltage

UB: DC 24 V (+/- 10 %)

Power consumption at UB = 24V

2.4 W (module enabled via S11. No load)

Number dual-channel inputs

1

Number start input

1 (auto-start or manual start each variant)

Max. switching capacity O1 ut UB.

max. 2.5 A (see derating in the operating instructions)

Maximum switching capacity auxiliary output C1

max. 100 mA

Max. switch-on delay

10 ms

Off-delay (if requested via the safety circuit)

< 13 ms

Ambient temperatur

-15 °C to 55 °C 
(see derating in the operating instructions)

Protection

IP20

Mounting

35 mm DIN-rail

PL; Kat.; SILCL (EN ISO 13849-1; EN 62061)

PL d; SILCL 2

Dimension

6.2 x 93.1 x 102.5 mm

Manual Start:

50 g

Manueller Start:

 

MINOS SL1D, tensil spring terminal, manual start

472800

MINOS SL1D, screw terminal,manual start

472801

MINOS SL2D, tensil spring terminal, manual start

472804

MINOS SL2D, screw terminal, manual start

472805

   

Auto-Start:

 

MINOS SL1D, tensil spring terminal, auto-start

472802

MINOS SL1D, screw terminal, auto-start

472803

MINOS SL2D, tensil spring terminal, auto-start

472806

MINOS SL2D, screw terminal, auto-start

472807