Click to reach us online

MINOS SLxE - EN 50156-1

Safe Firing MINOS SLxE - EN 50156-1

Features

  • Use up to PL, Cat. 4, SILCL3 (bound variant)
  • Stop category 0 according to EN 60204-1
  • 1 two-channel safe access
  • 1 safe solid state output (PNP)
  • 1 auxiliary output (PNP)
  • Automatic or monitored manual start
  • 6.2 mm width
  • Comprehensive monitoring with front LEDs

MINOS SLxE

Safety function

Safety emergency stop, safety doors, light curtains, contact reinforcement, OSSD, continous operation of furnaces , stopp category 0

Certified according to

EN ISO 13849-1; IEC 62061; IEC 61508;
EN 50156-1; EN 746-2IEC 61511-1; EN 60204-1

Approvals

CE, TUV

Operating voltage

UB: DC 24 V (+/- 10 %)

Power consumption at UB = 24V

2.4 W (module enabled via S11. No load)

Number dual-channel inputs

1

Number start input

1 (auto-start or manual start each variant)

Max. switching capacity O1 ut UB.

max. 2.5 A (see derating in the operating instructions)

Maximum switching capacity auxiliary output C1

max. 100 mA

Max. switch-on delay

10 ms

Off-delay (if requested via the safety circuit)

< 13 ms

Ambient temperatur

-15 °C to 55 °C 
(see derating in the operating instructions)

Protection

IP20

Mounting

35 mm DIN-rail

PL; Kat.; SILCL (EN ISO 13849-1; EN 62061)

PL e; SILCL 3

Dimension

6.2 x 93.1 x 102.5 mm

Weight

50 g

Manual Start:

 

MINOS SL1E, tensil spring terminal, manual start

472820

MINOS SL1E, screw terminal, manual start

472821

MINOS SL2E, tensil spring terminal, manual start

472824

MINOS SL2E, screw terminal, manual start

472825

Auto-Start:

 

MINOS SL1E, tensil spring terminal, auto-start

472822

MINOS SL1E, screw terminal, auto-start

472823

MINOS SL2E, tensil spring terminal, auto-start

472826

MINOS SL2E, screw terminal, auto-start

472827