Schneider Electric Ac Current Relays Model 3DM/FDM
■ Compact Design
■ 3DM:Panel Mounting Type
■ FDM:Panel Flush Mounting Type
■ MCU( Microprocessor Control Unit )&ASIC Based
■ Three Integral Current Transformers
■ Overcurrent/Phase Loss/Phase Reversal/Phase Unbalace/Locked Rotor
■ Digital Ammeter
■ Troubleshooting/Trip Cause Memory, Display
■ Adjustable Operating Features by Pulae Rotary switch
■ Wide Current Adjustment Range
■ Selectable Time-Current Characteristics(Inverse/Definite)
■ Manual Instantaneous/Electrical Remote Reset
■ Run time Monitor/Load Alert Function
■ Ambient Insensitive
■ Selectable Fail-safe and Non-fail-safe Operation Modes
EOCR Model 3DM/FDM Technical Specs
Protective Item
|
Trip Time
|
Over-current
|
DEF : 0.2 ~ 30sec INV : 1 ~ 30
|
Undercurrent
|
0.5~30sec(DEF)
|
|
within 3sec
|
|
0.1sec
|
|
8sec
|
Locked Rotor
|
Lock
|
0.5sec after dt
|
stall
|
1~10sec
|
A Lert
|
50~100% of Set Current
|
Model
|
3DM /FDM
|
Current Setting Range
|
Over-Current(oc)
|
0.1~800A(Over 20A with External CTs)
|
Under-Current(uc)
|
0.5~under OC setting
|
Time Setting
|
Starting Delay Time(dt)
|
OFF~200sec
|
Over-Current Trip (ot)
|
DEF:0.2~30sec/INV:1~30
|
Under-Current Trip (ut)
|
0.5~30sec(DEF)
|
Conrol Power
|
220
|
85~250VAC/DC, 85~50VAC/DC, 50/60Hz
|
Output Relay
|
O.L
|
2-SPST, 3A/250VAC, Resistive
|
A.L
|
1-SPST, 3A/250VAC, Resistive
|
Environment
|
Temperature
|
Store
|
-30 ~80 ℃
|
Operation
|
-30 ~60 ℃
|
Humidity
|
30~85%RH, Non-condensation
|
Display
|
7-Segment LEDs
|
3 Phase current, 3 Trip causes, Run time
|
|
Bar-Graph
|
% of existing Current vs OC setting current
|
Mounting
|
35mm DIN-Rail
|