EOCR Model 3DZ/FDZ

Schneider Electric Ac Current Relays Model 3DZ/FDZ

■ Compact Design 
■ MCU( Microprocessor Control Unit ) Based 
■ ASIC(Application Specific Integrated Circuit)Inside  
■ Three Integral Current Transformers 
■ Overcurrent/Phase Loss/Phase Reversal/Phase Unbalace/Locked Rotor/Ground Fault 
■ Digital Ammeter 
■ Troubleshooting/Trip Cause Memory, Display 
■ Adjustable Operating Features by DIP switch Setting 
■ Wide Current Adjustment Range  
■ Selectable Time-Current Characteristics(Inverse/Definite) 
■ Manual(Instantaneous)/Electrical(Remote)Reset 
■ Test Function 
■ Ambient Insensitive 
■ Selectable Fail-safe and Non-fail-safe Operation Modes 

EOCR Model 3DZ/FDZ

EOCR Model 3DD/FD Technical Specs

 

Protective Item

Trip Time

Over-current

DEF : 0.3 ~ 25sec         INV : 1 ~ 30

Phase Loss
within 4sec
Phase Unbalance
8sec
Phase Reversal
0.1sec
Locked Rotor
DEF : within 0.5sec after dt 
INV : If D-Time=0sec 
Operating according to Cold-curve 
If D-Time=Over 0sec 
Operating according to Hot-curve 
after D-time set
Ground Fault
1 or 0.03sec

 

over Current Setting

Type

Setting Range

05

0.5 ~ 6/10A
20
5 ~ 20A
100

10 ~ 120A

Wth External CTs
150

15 ~ 180A

200

20 ~ 240A

300
30 ~ 360A

400

40 ~ 480A

500

50 ~ 600A
600
60 ~ 720A
Ground Fault Current Setting
A
0.05~2.5A

B

0.2~10A

Start Delay Time Setting(D-TIME)

SW3-INV/On

0~120sec

SW3-DEF/Off
1~120sec

Trip Time Setting (O-TIME)

SW3-INV/On
1-30
 
 
SW3-DEF/Off
 
0.3-25sec

Conrol Voltage

85-250VAC/DC
Output Relay
O.L
1-SPST(1b), 3A/250VAC Resistive
G.R
1-SPST(1a), 3A/250VAC Resistive
Time Characteristic
SW3-INV/On
Inverse
SW3-DEF/Off
Definite
Trobleshooting/Trip Indication
 
LED Display
Current Sensing
3-CT

Mounting

35mm DIN-Rail/Panel