Click to reach us online

EOCR Model 3MS/FMS

Schneider Electric Ac Current Relays Model 3MS/DMS

■ Compact Design 
■ 3MS:Panel Mounting Type 
■ FMS:Panel Flush Mounting Type 
■ MCU( Microprocessor Control Unit )&ASIC Based
■ Three Integral Current Transformers 
■ Overcurrent/Phase Loss/Phase Reversal/Phase Unbalace/Locked Rotor/Short Circuit 
■ Digital Ammeter 
■ Troubleshooting/Trip Cause Memory, Display 
■ Adjustable Operating Features by Pulae Rotary switch 
■ Wide Current Adjustment Range  
■ Selectable Time-Current Characteristics(Inverse/Definite) 
■ Manual Instantaneous/Electrical Remote Reset 
■ Fast Short Circuit protection 
■ Ambient Insensitive 
■ Selectable Fail-safe and Non-fail-safe Operation Modes

EOCR Model 3MS/FMS

EOCR Model 3MS/FMS Technical Specs

Protective Item

Trip Time

Over-current

DEF : 0.2 ~ 30sec      INV : 1 ~ 30

Undercurrent
0.5~30sec(DEF)
Phase Loss
within 3sec
Phase Unbalance
0.1sec
Phase Reversal
8sec
Locked Rotor
Lock
0.5sec after dt
stall
1~10sec
Short Circuit
within 0.05sec

 

Model

3MS/FMS

Current Setting Range
Over-Current(oc)
0.1~800A(Over 20A with External CTs)
Under-Current(uc)
0.5~under OC setting
Short Circuit (Sc)
300~1800% of set current

Time Setting

Starting Delay Time(dt)
OFF~200sec
Over-Current Trip (ot)
DEF:0.2~30sec/INV:1~30
Under-Current Trip (ut)
0.5~30sec(DEF)

 

Conrol Power

220
85~250VAC/DC, 50/60Hz
Output Relay
O.L
2-SPST, 3A/250VAC, Resistive
S.H
1-SPST, 3A/250VAC, Resistive
Environment
Temperature
 
Store
-30 ~80 ℃
Operation
-30 ~60 ℃
Humidity
30~85%RH, Non-condensation
Display
7-Segment LEDs
3 Phase current, 3 Trip causes, Run time
 
Bar-Graph
% of existing Current vs OC setting current
Mounting
35mm DIN-Rail